Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

Version 1 Next »

Use this Quick Reference Guide to learn more about the Overview Page.

The Overview page provides a summary of operating conditions.

The screen includes Digital Gauges, Pump Widgets, and Historical Trend.

Pump Header

Click the pump header to navigate to the pump’s overview screen.

Or toggle Curves/Settings/None to display performance on the pump curve, settings, or collapse the header to expand the chart view.

The header displays flow, speed (if on a VFD), and time since last start/stop.

The color in the top left corner of the header determines each pump’s fill color on the trend.

Pump Header (continued)

Its fill color indicates the pump’s status: running (green), off (gray), or faulted (orange).

For sites operating in Advisory Mode, a red bubble atop the header provides a % speed recommendation.

Digital Gauges

The outputs of key operating parameters are shown to the left of the screen.

Historical Trend

The graph charts the operating history of the station.

Graphed tags are displayed in the legend at the bottom. The color of the legend entry matches the color of the line.

Tags may be hidden from graph view by clicking the tag in the legend.

Tank Level Constraints

If configured, a summary of source and target tank constraints will display at the bottom left.

  • No labels

0 Comments

You are not logged in. Any changes you make will be marked as anonymous. You may want to Log In if you already have an account.