Use this Quick Reference Guide to learn more about the Overview Page.
Overview page provides a summary of operating conditions. The screen includes Digital Gauges, Level Settings, Pump Widgets, and Historical Trend. | |||
Pump Header Click the pump header to navigate to the pump’s overview screen. Or toggle Curves/Settings/None to display performance on the pump curve, settings, or collapse the header to expand the chart view. The header displays flow, speed (if on a VFD), and time since last start/stop.
| |||
Controls When Tagger is online and the pumps are in auto, it will operate by the start/stop levels in the tank bar graph. Second, if start/stop levels are set incorrectly (or control isn’t working), the PLC will operate by physical floats. It will run all available pumps to do so. Finally, in an emergency or in a maintenance setting, the physical HOA overrides both previous controls. | |||
Historical Trend The graph charts the operating history of the station. Graphed tags are displayed in the legend at the bottom. The color of the legend entry matches the color of the line.
|
Not quite what you need? Return to the Help HOMEScreen.