Overview Page (Lift Station Guardian)

Use this Quick Reference Guide to learn more about the Overview Page.

Overview page provides a summary of operating conditions.

The screen includes Digital Gauges, Level Settings, Pump Widgets, and Historical Trend.

Pump Header

Click the pump header to navigate to the pump’s overview screen.

Or toggle Curves/Settings/None to display performance on the pump curve, settings, or collapse the header to expand the chart view.

The header displays flow, speed (if on a VFD), and time since last start/stop.

The color in the top left corner of the header determines each pump’s fill color on the trend.

Its fill color indicates the pump’s status: running (green), off (gray), or faulted (orange).

 

 

 

 

Controls

When Tagger is online and the pumps are in auto, it will operate by the start/stop levels in the tank bar graph.

Second, if something prevents Tagger from being able to control, the PLC will operate by physical floats. It will run all available pumps to do so.

Finally, in an emergency or in a maintenance setting, the physical HOA overrides both previous controls.

Historical Trend

The graph charts the operating history of the station.

Graphed tags are displayed in the legend at the bottom. The color of the legend entry matches the color of the line.

Tags may be hidden from graph view by clicking the tag in the legend.

 

 

 

Not quite what you need? Return to the Help HOME Screen.